5.3.3.Serving TIWAY data map descriptor example

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

TIWAY_Data_Type,

Address,

Length

S01_RAW16_PLC0,

RAW16_Data,

0,

Server,

PLC_01,

IE_Ladder,

0,

10

The above map descriptor serves 10 data elements starting from address 0 of type “IE_Ladder” for PLC_01.

5.3.4.Serving Drum_Count_Preset TIWAY data map descriptor example

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

TIWAY_Data_Type, Address,

Length,

S10_RAW16_PLC01,

RAW16_Data,

71,

Server,

PLC_01,

Drum_Count_Preset, 0,

4,

Preset_Step_List

 

 

 

 

 

 

3 5 9 167

 

 

 

 

 

 

The above map descriptor serves 4 data elements starting from address 0 of type “Drum_Count_Preset” for PLC_01. Each address location is contiguously associated with a preset step value from the Preset_Step_List field.

5.3.5.Serving PLC status data map descriptor example

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

TIWAY_Data_Type,

Length

S36_PRIM_STATUS,

Status,

0,

Server,

PLC_01,

Status_Primitive,

3

The above map descriptor serves 3 status data elements for PLC_01 in the data array “Status” starting from offset 0.