FS-8700-31 Siemens TIWAY I

Page 4 of 23

the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

 

Section Title

 

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

 

Column Title

 

Function

 

 

Legal Values

 

 

Data_Array_Name

 

Provide name for Data Array

 

 

Up to 15 alphanumeric

 

 

 

 

 

characters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Float, Bit, UInt16, SInt16,

 

 

Data_Array_Format

 

Provide data format. Each Data Array

 

 

Packed_Bit, Byte,

 

 

 

can only take on one format.

 

 

Packed_Byte,

 

 

 

 

 

 

 

 

 

 

 

 

 

Swapped_Byte

 

 

 

 

Number of Data Objects. Must be

 

 

 

 

 

Data_Array_Length

 

larger than the data storage area

 

1-10,000

 

 

 

required by the map descriptors for

 

 

 

 

 

 

 

 

 

 

 

 

the data being placed in this array.

 

 

 

 

 

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

// Data Arrays

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

Data_Array_Name,

Data_Format,

 

Data_Array_Length,

 

 

RAW16_Data,

UInt16,

20

 

 

RAW8_Data,

Byte,

20

 

 

Float_Data,

Float,

20

 

 

 

 

 

 

 

 

 

4.2.Client Side Connection Descriptions

 

Section Title

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

Column Title

 

 

Function

 

 

Legal Values

 

 

 

 

 

Specify which port the device

 

 

 

 

 

Port

 

 

is connected to the

 

 

P1-P8

 

 

 

 

 

FieldServer

 

 

 

 

 

Protocol

 

Specify protocol used

 

TIWAY, TIWAY_BDLC

 

 

Baud*

 

 

Specify baud rate

 

 

110 – 115200, standard

 

 

 

 

 

 

baudrates only

 

 

 

 

 

 

 

 

 

 

Parity*

 

 

Specify parity

 

Even, Odd, None, Mark, Space

 

 

Data_Bits*

 

 

Specify data bits

 

7, 8

 

 

Stop_Bits*

 

 

Specify stop bits

 

1

 

 

Handshaking*

 

Specify hardware handshaking

 

RTS, RTS/CTS, None

 

 

Poll _Delay*

 

 

Time between internal polls

 

0-32000 seconds, 1 second

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com