FS-8700-31 Siemens TIWAY I

Page 15 of 23

4.4.6.6.Reset Adapter

Forces the UNILINK Host Adapter to do a hardware reset.

Map_Descriptor_Name,

Data_Array_Name, Data_Array_Offset,

Function,

Node_name,

TIWAY_Host_Adapter_Cmd,

Length

C42_RESET_ADAPTER,

Cmd_Triggers,

1,

AWT,

PLC_01,

Reset_Adapter,

1

The above map descriptor will execute the indicated host adapter command once every time a value is written to the data array “Cmd_Triggers” at offset 1.

4.4.6.7.Disconnect Secondaries

Disconnect Secondary PLCs from the network.

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

TIWAY_Host_Adapter_Cmd,

Length,

C43_DISC_SECDS,

Cmd_Triggers,

2,

AWT,

PLC_01,

Disconnect_Secondaries,

1,

Secondaries_List

 

 

 

 

 

 

1 9 147 254

 

 

 

 

 

 

The above map descriptor will execute the indicated host adapter command once every time a value is written to the data array “Cmd_Triggers” at offset 2. Secondaries 1 9 147 and 254 will be disconnected from the network.

To disconnect all secondaries, use only one value of 255 in the Secondaries_List field.

4.4.6.8.Connect Secondaries

Disconnect Secondary PLCs from the network.

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

TIWAY_Host_Adapter_Cmd,

Length,

C45_CONNECT_SECDS,

Cmd_Triggers,

4,

AWT,

PLC_01,

Connect_Secondaries,

1,

Secondaries_List

 

 

 

 

 

 

1 9 147 254

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 18
Image 18
FieldServer FS-8700-31 instruction manual Reset Adapter, Disconnect Secondaries, Connect Secondaries