The above map descriptor will continuously execute the indicated host adapter command and will store the following parameter values in the data array “HIU_Config”:

Offset Parameter

0Dipswitch 1 and 2 settings

1Config flag ( 0 = HIU not configured, 1 = HIU configured )

2Option 01 configuration value

3Option 02 configuration value

4Option 03 configuration value

4.4.6.3.Report Adapter Configuration

Reports the Adapter Configuration option values that was used to configure the adapter.

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

TIWAY_Host_Adapter_Cmd,

Length,

C39_REP_ADAP_CONFIG,

Adapter_Config,

0,

RDBC,

PLC_01,

Report_Adapter_Config,

6,

Scan_Interval

 

 

 

 

 

 

0s

 

 

 

 

 

 

The above map descriptor will continuously execute the indicated host adapter command and will store the following parameter values in the data array “Adapter_Config”:

Offset Parameter

0Dipswitch 1 and 2 settings

1Config flag ( 0 = Adapter not configured, 1 = Adapter configured )

2Option 01 configuration value

3Option 02 configuration value

4Option 03 configuration value

5Option 04 configuration value

4.4.6.4.Report Network Manager Configuration

Reports the Network Manager option values that was used to configure the network manager.

Map_Descriptor_Name,

Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Host_Adapter_Cmd, Length,