FS-8700-931 Siemens TIWAY I

Page 17 of 23

5.Configuring the FieldServer as a TIWAY Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer instruction Configuration mManual (Virtual PLC). The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a TIWAY Client.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for TIWAY communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1.Server Side Connection Descriptors

 

Section Title

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

Column Title

 

 

Function

 

 

Legal Values

 

 

Port

 

 

Specify which port the device is

 

 

P1-P8

 

 

 

 

connected to the FieldServer

 

 

 

 

 

 

 

 

 

 

 

 

Protocol

 

 

Specify protocol used

 

TIWAY, TIWAY_BDLC

 

 

Baud*

 

 

Specify baud rate

 

 

110 – 115200, standard

 

 

 

 

 

 

baud rates only

 

 

 

 

 

 

 

 

 

 

Parity*

 

 

Specify parity

 

 

Even, Odd, None, Mark,

 

 

 

 

 

 

Space

 

 

 

 

 

 

 

 

 

 

Data_Bits*

 

 

Specify data bits

 

7, 8

 

 

Stop_Bits*

 

 

Specify stop bits

 

1

 

 

Handshaking*

 

Specify hardware handshaking

 

RTS, RTS/CTS, None

 

 

 

 

 

Specifies time FieldServer will

 

 

 

 

 

Server_Hold_Timeout*

 

 

reserve server side connection

 

 

>1.0s

 

 

 

 

while waiting for the Client side

 

 

 

 

 

 

 

to update data in Data_Array (if

 

 

 

 

 

 

 

 

necessary)

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 20
Image 20
FieldServer FS-8700-31 instruction manual Configuring the FieldServer as a Tiway Server, Server Side Connection Descriptors