FS-8700-31 Siemens TIWAY I

 

 

 

 

Page 14 of 23

C40_REP_NM_CONFIG,

Nm_Config,

0,

RDBC,

PLC_01,

Report_NM_Config,

16,

Scan_Interval

 

 

 

 

 

 

0s

 

 

 

 

 

 

The above map descriptor will continuously execute the indicated host adapter command and will store the following parameter values in the data array “Nm_Config”:

Offset Parameter

0Dipswitch 1 and 2 settings

1Config flag ( 0 = Network Manager not configured, 1 = Network Manager configured )

2Option 01 configuration value

3Option 02 configuration value

4Option 03 configuration value

5Option 04 configuration value

6Option 05 configuration value

7Option 06 configuration value

8Option 07 configuration value

9Option 08 configuration value

10Option 09 configuration value

11Option 0A configuration value

12Option 0B configuration value

13Option 0C configuration value

14Option 0D configuration value

15Option 0E configuration value

4.4.6.5.Soft Reset

Forces the UNILINK Host Adapter to do a software reset.

Map_Descriptor_Name,

Data_Array_Name, Data_Array_Offset,

Function,

Node_name,

TIWAY_Host_Adapter_Cmd,

Length

C41_SOFT_RESET,

Cmd_Triggers,

0,

AWT,

PLC_01,

Soft_Reset,

1

The above map descriptor will execute the indicated host adapter command once every time a value is written to the data array “Cmd_Triggers” at offset 0.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 17
Image 17
FieldServer FS-8700-31 instruction manual Soft Reset, Forces the Unilink Host Adapter to do a software reset