FS-8700-84_Lutron_eLumen Driver Manual

Page 14 of 36

4.1.11.System Monitor Command – Timeclock Status

//Client side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

 

Scan_Interval,

 

Data_Array_Name,

Data_Array_Offset,

 

Function,

 

Node_Name,

GRAFIK

_command,

Area,

Length

Tclk_sts_00,

 

1s,

 

 

Tclk_status,

0,

 

rdbc,

 

LUT_GRF6_0,

timeclock_status,

0,

4

Tclk_sts_01,

 

1s,

 

 

Tclk_status,

4,

 

rdbc,

 

LUT_GRF6_0,

timeclock_status,

1,

4

Data storage in Data Array

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Position from offset

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

Schedule number

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

Next event type (1 = no more events, 2 = timeclock disabled, 3 = astronomic event, 4 = realtime event )

 

2

 

 

Next event time ( minutes past midnight )

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

Next script

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: This command stores 4 data values. To prevent overlaps, remember to increment Data_Array_Offset by 4 when referencing the same Data Array with other Map Descriptors.

4.1.12.System Monitor Command – Zone Intensity

//Client side Map Descriptors

Map_Descriptors

Map_Descriptor_Name,

 

Scan_Interval,

 

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

Zone,

Length

Zn_int_00,

 

1s,

 

 

Zone_int,

0,

rdbc,

LUT_GRF6_0,

zone_intensity,

0,

1

Zn_int_01,

 

1s,

 

 

Zone_int,

1,

rdbc,

LUT_GRF6_0,

zone_intensity,

1,

1

Data storage in Data Array

 

 

 

 

 

 

 

 

 

Position from offset

 

 

Description

 

 

 

 

 

 

0

 

 

Zone intensity ( 0-127 )

 

 

 

 

 

 

Note: This command stores 1 data value. To prevent overlaps, remember to increment Data_Array_Offset by 1 when referencing the same Data Array with other Map Descriptors.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Page 17
Image 17
FieldServer FS-8700-84 instruction manual System Monitor Command Timeclock Status, System Monitor Command Zone Intensity