FS-8700-84_Lutron_eLumen Driver Manual

Page 25 of 36

4.1.33.System Control Commands containing no Parameters: Simulate wallstation(s) switch press

//Client side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Ws_sw_press,

Lut_triggers,

16,

awt,

LUT_GRF6_0,

sim_ws_sw_press,

Sim_sw_list,

0,

1

DA_Lut_List data setup

 

Position from DA_Lut_List_Offset

Description

0

Link number ( 0-11 )

1

Station of link ( 0-31 ) of Switch ID 0

2

Switch on station ( 0-31 ) of Switch ID 0

3

Station of link ( 0-31 ) of Switch ID 1

4

Switch on station ( 0-31 ) of Switch ID 1

..

..

63

Station of link ( 0-31 ) of Switch ID 31

64

Switch on station ( 0-31 ) of Switch ID 31

Note: 1 to 32 switch ids may be used in a single command. To trigger the command, write the number of switch IDs into the Data Array specified by Data_Array_Name at Data_Array_Offset.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Page 28
Image 28
FieldServer FS-8700-84 instruction manual Link number