4.1.31.System Control Commands containing no Parameters: Enable wallstation(s)

// Client side Map Descriptors Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Enable_ws,

Lut_triggers,

14,

awt,

LUT_GRF6_0,

ena_wallstation,

Ctrl_ws_list,

0,

1

DA_Lut_List data setup

Position from DA_Lut_List_Offset 0 1

..

62

63

Description

Link number ( 0-11 ) of Station ID 0 Station on link ( 0-31 ) of Station ID 0

..

Link number ( 0-11 ) of Station ID 31 Station on link ( 0-31 ) of Station ID 31

Note: 1 to 32 station ids may be used to enable wallstations. To trigger the command, write the number of station IDs into the Data Array specified by Data_Array_Name at Data_Array_Offset

4.1.32.System Control Commands containing no Parameters: Disable wallstation(s)

// Client side Map Descriptors Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Disable_ws,

Lut_triggers,

15,

awt,

LUT_GRF6_0,

dis_wallstation,

Ctrl_ws_list,

0,

1

DA_Lut_List data setup

Position from DA_Lut_List_Offset 0 1

..

62

63

Description

Link number ( 0-11 ) of Station ID 0 Station on link ( 0-31 ) of Station ID 0

..

Link number ( 0-11 ) of Station ID 31 Station on link ( 0-31 ) of Station ID 31

Note: 1 to 32 station ids may be used to disable wallstations. To trigger the command, write the number of station IDs into the Data Array specified by Data_Array_Name at Data_Array_Offset.