Page 26 of 36 |
4.1.34.System Control Commands containing no Parameters: Simulate wallstation(s) switch release
// Client side Map Descriptors Map_Descriptors
Map_Descriptor_Name, | Data_Array_Name, | Data_Array_Offset, | Function, | Node_Name, | GRAFIK_command, | DA_Lut_List, | DA_Lut_List_Offset, | Length |
Ws_sw_rls, | Lut_triggers, | 17, | awt, | LUT_GRF6_0, | sim_ws_sw_rls, | Sim_sw_list, | 0, | 1 |
DA_Lut_List data setup |
|
|
|
|
|
|
| |
Position from DA_Lut_List_Offset | Description |
|
|
|
|
|
| |
0 |
| Link number ( |
|
|
|
|
| |
1 |
| Station of link ( |
|
|
|
| ||
2 |
| Switch on station ( |
|
|
| |||
3 |
| Station of link ( |
|
|
|
| ||
4 |
| Switch on station ( |
|
|
| |||
.. |
| .. |
|
|
|
|
|
|
63 |
| Station of link ( |
|
|
|
| ||
64 |
| Switch on station ( |
|
|
|
Note: 1 to 32 switch ids may be used in a single command. To trigger the command, write the number of switch IDs into the Data Array specified by Data_Array_Name at Data_Array_Offset.
4.1.35.System Control Commands containing no Parameters: Stop scene ramp down
// Client side Map Descriptors Map_Descriptors
Map_Descriptor_Name, | Data_Array_Name, | Data_Array_Offset, | Function, | Node_Name, | GRAFIK_command, | DA_Lut_List, | DA_Lut_List_Offset, | Length |
Stop_scn_rmp_dn, | Lut_triggers, | 18, | awt, | LUT_GRF6_0, | stop_scene_ramp_dn, | Area_list, | 0, | 1 |
DA_Lut_List data setup |
|
|
|
|
|
|
| |
Position from DA_Lut_List_Offset | Description |
|
|
|
|
|
| |
| Area(s) with scenes to stop ramp down |
|
|
|
Note: After setting up the area numbers to stop scene ramps in the DA_Lut_List Data Array, trigger this command by writing the number of areas into the Data Array specified by Data_Array_Name at an offset specified by Data_Array_Offset.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408)