4.1.34.System Control Commands containing no Parameters: Simulate wallstation(s) switch release

// Client side Map Descriptors Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Ws_sw_rls,

Lut_triggers,

17,

awt,

LUT_GRF6_0,

sim_ws_sw_rls,

Sim_sw_list,

0,

1

DA_Lut_List data setup

 

 

 

 

 

 

 

Position from DA_Lut_List_Offset

Description

 

 

 

 

 

 

0

 

Link number ( 0-11 )

 

 

 

 

 

1

 

Station of link ( 0-31 ) of Switch ID 0

 

 

 

 

2

 

Switch on station ( 0-31 ) of Switch ID 0

 

 

 

3

 

Station of link ( 0-31 ) of Switch ID 1

 

 

 

 

4

 

Switch on station ( 0-31 ) of Switch ID 1

 

 

 

..

 

..

 

 

 

 

 

 

63

 

Station of link ( 0-31 ) of Switch ID 31

 

 

 

 

64

 

Switch on station ( 0-31 ) of Switch ID 31

 

 

 

Note: 1 to 32 switch ids may be used in a single command. To trigger the command, write the number of switch IDs into the Data Array specified by Data_Array_Name at Data_Array_Offset.

4.1.35.System Control Commands containing no Parameters: Stop scene ramp down

// Client side Map Descriptors Map_Descriptors

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

GRAFIK_command,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Stop_scn_rmp_dn,

Lut_triggers,

18,

awt,

LUT_GRF6_0,

stop_scene_ramp_dn,

Area_list,

0,

1

DA_Lut_List data setup

 

 

 

 

 

 

 

Position from DA_Lut_List_Offset

Description

 

 

 

 

 

 

0-31

 

Area(s) with scenes to stop ramp down

 

 

 

Note: After setting up the area numbers to stop scene ramps in the DA_Lut_List Data Array, trigger this command by writing the number of areas into the Data Array specified by Data_Array_Name at an offset specified by Data_Array_Offset.