FS-8700-84_Lutron_eLumen Driver Manual

Page 6 of 36

1.04Client Side Connection Descriptions

 

Section Title

 

 

 

 

 

Connections

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

 

 

Specify which port the

 

P1-P8, R1-R21

 

Port

 

device is connected to the

 

 

 

 

FieldServer

 

 

 

Protocol

Specify protocol used

eLumen

 

Baud*

 

Specify baud rate

 

9600 – Vendor limitation

 

Parity*

Specify parity

 

None

 

Data_Bits*

 

Specify data bits

8

 

Stop_Bits*

 

Specify stop bits

1

 

Handshaking*

 

Specify hardware

 

None

 

 

handshaking

 

 

 

 

 

 

 

Poll _Delay*

Time between internal polls

 

0-32000 seconds, 1 second

Example

//Client Side Connections

Connections

Port,

Protocol,

Baud,

Parity,

Data Bits,

Stop Bits,

Poll_Delay

P1,

eLumen,

9600,

None,

None,

1,

0.100s

1.05Client Side Node Descriptors

 

Section Title

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

 

Node_Name

 

Provide name for node

 

Up to 32 alphanumeric

 

 

 

characters

 

 

 

 

 

 

 

 

The eLumen processor

 

 

 

 

Node_ID

 

address - only decimal values

0-255

 

 

 

allowed e.g. 11 hex has to be

 

 

 

 

 

 

 

 

 

 

entered as 17.

 

 

 

 

Protocol

Specify protocol used

eLumen

 

Port

 

Specify which port the device is

 

P1-P8, R1-R21

 

 

 

connected to the FieldServer

 

 

 

 

Node_type

 

Specifies the eLumen

 

Hex, decimal

 

 

command and data format

 

 

 

 

 

 

 

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com