4.2.Client Side Connection Descriptors

Section Title

 

 

 

 

 

 

Adapter

 

 

 

 

 

 

Column Title

 

 

Function

Legal Values

 

Adapter

 

Adapter Name

 

N1, N22

 

Protocol

 

Specify protocol used

SNMP

 

 

 

If this parameter is omitted or set to 0 the short form of

 

 

 

 

 

encoding length will be used. If the parameter is set to

 

 

 

 

 

1 (and the Length is ≤ 127) the long form of encoding

 

 

 

 

 

length will be used. For Length >127 short form will

 

 

 

 

 

be used regardless of the setting.

0 (default),

 

Length_Encode_Method

 

 

 

 

 

1

 

 

 

 

Long form: an extra byte will be inserted to indicate

 

 

 

 

the number of following bytes which indicates the

 

 

 

 

 

length of the following section in message.

 

 

 

 

 

Short form: only length value will be inserted.

 

 

 

 

 

This parameter can be configured if it is required that

Any string up to

 

SNMP_Community*

 

“Community” be a different name in order to receive

255 characters,

 

 

 

traps.

 

Public

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

// Client Side Connections

 

 

 

 

Adapters

 

 

 

 

 

 

Adapter,

Protocol,

Length_Encode_Method

 

 

 

N1,

SNMP,

1

 

 

 