FS-8704-16 Omron FINS Manual

 

Page 8 of 37

 

 

Example

 

 

 

 

 

 

 

 

 

// Client Side

 

 

 

 

Connections

 

 

 

 

Adapters

 

 

 

 

Adapter,

Protocol,

Udp_port_number

 

 

N1,

Fins,

9600

 

1.08Client Side Node Descriptors

Section Title

 

 

Nodes

 

 

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric

characters

 

 

IP_Address

Provide IP Address of PLC

Eg. 192.168.1.105

 

Node number set at PLC

 

 

The node number should

 

Node_ID

correspond to the last byte of

1-126

 

the IP address. Eg. 105

 

 

corresponds to the example IP

 

 

address above.

 

Protocol

Specify protocol used

Fins, omn_fins or fins_udp

Adapter

Specify which port the device is

N1, N23

 

connected to the FieldServer

 

*Net_Number

Provide the network number of

1-255

PLC

 

 

Example

 

 

//Client Side Nodes

Nodes

 

 

 

 

 

Node_Name,

IP_Address,

Node_ID,

Protocol,

Adapter,

Net_Number

PLC 1,

192.168.1.5,

1,

Fins,

N1,

1

3Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 11
Image 11
FieldServer FS-8704-16 instruction manual Plc