FieldServer FS-8704-16 instruction manual Cio-Word, Wr-Word

Models: FS-8704-16

1 40
Download 40 pages 6.81 Kb
Page 20
Image 20

FS-8704-16 Omron FINS Manual

Page 17 of 37

1.012

Server Side Map Descriptors

 

5.1.1.FieldServer Specific Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name

Name of this Map

Up to 32 alphanumeric

Descriptor

characters

 

 

Name of Data Array

One of the Data Array names

Data_Array_Name

where data is to be

from “Data Array” section

 

stored in the FieldServer

above

Data_Array_Offset

Starting location in Data

0 to maximum specified in

Array

“Data Array” section above

 

Function

Function of Server Map

Server

Descriptor

 

 

 

 

 

5.1.2.Driver Specific Map Descriptor Parameters

Column Title

Function

Legal Values

 

Name of Node to fetch

One of the node names

Node_Name

specified in “Server Node

data from

 

Descriptor” above

 

 

*Data_Type

 

CIO-WORD, WR-WORD,

Data type

HR-WORD, AR-WORD,

(see Note1 Appendix A.1)

 

EM-WORD

 

 

 

 

 

Length

Length of Map Descriptor

1 to maximum specified in

Data Array section above

 

 

*Address

Starting address of read

0,100, 32767 etc

block

see section 6.1 for detail

 

*Memory_Code

Memory code for PLC

B0, B1, B2, B3, 82, 98 and

(see Note1 Appendix A.1)

memory type

A0 ---- AC

 

 

MEMORY AREA READ

 

 

MEMORY AREA WRITE

*Command_Name

 

RUN-STOP

Name of the command

CLOCK READ

(see Note2 Appendix A.1)

 

CLOCK WRITE

 

 

 

 

CYCLE TIME READ

 

 

CPU UNIT STATUS READ

*MRC

Main Request Code

1,4,6,7

(see Note2 Appendix A.1)

 

 

*SRC

Sub Request Code

1,2,20

(see Note2 Appendix A.1)

 

 

*Unit_Number

Unit number of CPU at

0,1,2 etc

PLC

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 20
Image 20
FieldServer FS-8704-16 instruction manual Cio-Word, Wr-Word