FS-8704-16 Omron FINS Manual

 

Page 7 of 37

 

Example

 

 

 

 

 

 

 

// Data Arrays

 

 

 

Data_Arrays

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length,

 

DA_CIO,

UInt16,

5143

 

DA_WR,

UInt16,

511

 

DA_HR,

Uint16,

511

 

DA_DM,

Uint16,

32767

1.06Driver Specific FieldServer Parameters

Section Title

 

 

FieldServer

 

 

Column Title

Function

Legal Values

Title

Name for FieldServer

Text

 

Specify physical node Id on

 

 

network.

 

 

This is the last byte of the

 

 

IP Address of the

 

System_Node_Id

FieldServer. eg. If

1-126

 

FieldServer’s IP Address is

 

 

192.168.1.81 then this

 

 

parameter should be set to

 

 

81

 

Example

 

 

//FieldServer Driver specific parameters FieldServer

Title,

 

System_Node_Id

Fins Client,

 

81

1.07Client Side Connection Descriptors

Section Title

 

 

Adapter

 

 

Column Title

Function

Legal Values

Adapter

Adapter Name

N1, N22

Protocol

Specify protocol used

Fins, omn_fins or fins_udp

Udp_port_number

Specify UDP port number

0, 9600 etc

2Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 10
Image 10