5.Configuring the FieldServer as a FINS Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver CD).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a FINS Client.

As a Server, the Driver responses to read requests and updates the FieldServer Data Arrays with write requests from the Client.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for FINS communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

1.010

Server Side Connection Descriptors

 

 

 

 

 

 

 

 

Section Title

 

 

 

Adapter

 

 

 

 

Column Title

Function

Legal Values

 

Adapter

Adapter Name

N1, N24

 

Protocol

Specify protocol used

Fins, omn_fins or fins_udp

 

Udp_port_number

Specify UDP port number

0,9600 etc

 

Example

 

 

 

 

 

 

 

 

//

Server Side

 

 

 

Connections

 

 

 

Adapters

 

 

 

Adapter,

Protocol,

Udp_port_number

 

N1,

Fins,

9600