Fluke T100/120/140
Users Manual
Voltage Test with RCD Trip Test
(only T140 VDE)
1)Press Button on rear side - measurement point light (10).
2)Measure between L and PE.
3)The RCD is tripping
The RCD could be so long tripped like the measuring point lighting is active and L is measured against PE. After a voltage test wait approx.. 50 seconds to trip the RCD again.
Restistance Test (only T140 / T140 VDE)
Make sure that UUT is not live.
•Check that UUT is not live by carrying out a
•Connect both test probes with UUT. Press Button on rear side - for measurement point light (10) and read value on the display.
The resistance range is 1…1999 Ω at a resolution of 1 Ω.
The resistance test is active for 20 se- conds after having pressed the button on the rear.
If during the resistance measurement a voltage is present the instrument switch automatically to voltage measurement.
Continuity Test / Diode Test
Make sure that UUT is not live. Test volta- ge polarity at handle test probe is positive
(+).
•Check that UUT is not live by carrying out a
•Connect both test probes with UUT. A signal sound is audible for continuity and the LED for continuity Rx/Ω is illuminated.
9