GE Energy Services
ANSI X3.28/SRIO DPA
CONFIGURATION GUIDE
A071-0CG-2.02-2 Restricted
2 Full
1.2 Configuration Sequence
The following is a list of the steps required to configure the ANSI X3.28/SRIO DPA:
1. Edit the configuration for the other applications that will run on the product. Prepare them
according to their own configuration guides. The SPABUS DCA must be configured before
the ANSI X3.28/SRIO DPA.
2. Edit the ANSI X3.28/SRIO DPA configuration. Prepare it according to the guidelines in this
document and the specific use for which the ANSI X3.28/SRIO DPA is required.
3. Generate the configuration and download it to the product using a GE Energy Services
Configuration System. The list of applications to be compiled must include the ANSI
X3.28/SRIO DPA, application A071, and the SPABUS DCA, application A070.
4. Restart the product. If the ANSI X3.28/SRIO DPA encounters an error during its
initialization, it will log a message to the WESMAINT Error Log and then, depending on the
severity of the error, terminate or continue with its run-time function.
5. Check for error messages. Log into the WESMAINT maintenance interface, select the
SYSTEM FUNCTIONS item from the Main Menu, and then select the ERROR LOG item
from the System Functions Menu. If any error messages are displayed, correct the problem as
described in Appendix B: ERROR MESSAGES, and repeat steps 3 through 5.
When the ANSI X3.28/SRIO DPA has successfully validated all the configuration parameters,
configuration is complete.