ANSI X3.28/SRIO DPA

 

CONFIGURATION GUIDE

GE Energy Services

Invalid parity configured (N)one, (E)ven, (O)dd

Cause:

The configured parity is invalid.

Remedy:

Ensure the configured Parity in A071MAIN is either None (N), Even (E), or Odd (O).

Invalid PD offset configured

Cause:

The configured parameter data partition offset is invalid.

Remedy:

Ensure the configured PD Offset in A071MAIN is a positive value.

Ensure the configured PD Offset is less than the TM Offset.

Invalid Retransmit analog configured -1 to 255

Cause:

The number of analog event data retries configured is invalid.

Remedy:

Ensure the number of AI Retries configured in A071MAIN is in the range -1 through 255. (- 1 indicates try forever.)

Invalid Retransmit digital configured -1 to 255

Cause:

The number of digital event data retries configured is invalid.

Remedy:

Ensure the number of DI Retries configured in A071MAIN is in the range -1 through 255. (- 1 indicates try forever.)

Invalid Retransmit ev data configured -1 to 255

Cause:

The number of EV event data retries configured is invalid.

Remedy:

Ensure the number of EV Retries configured in A071MAIN is in the range -1 through 255. (- 1 indicates try forever.)

Invalid Re-transmit event configured -1 to 255

Cause:

The number of SPA event data retries configured is invalid.

Remedy:

Ensure the number of SPA Event Retries configured in A071MAIN is in the range -1 through 255. (-1 indicates try forever.)

Restricted

A071-0CG-2.02-2

Full

17

 

Page 29
Image 29
GE A071-0CG manual Invalid parity configured None, Even, Odd, Invalid PD offset configured