ANSI X3.28/SRIO DPA

 

CONFIGURATION GUIDE

GE Energy Services

Invalid DD offset configured

Cause:

The configured direct data offset is invalid.

Remedy:

Ensure the configured DD Offset in A071MAIN is a positive value.

Ensure the configured DD Offset is less than the Sys Offset.

Invalid destination number

Cause:

The configured RTU address is invalid.

Remedy:

Ensure the configured RTU Address in A071MAIN is not the broadcast address (255).

Invalid DI offset configured

Cause:

The configured digital input offset is invalid.

Remedy:

Ensure the configured DI Offset in A071MAIN is a positive value.

Ensure the configured DI Offset is less than the DO Offset.

Invalid DO offset configured

Cause:

The configured digital output offset is invalid.

Remedy:

Ensure the configured DO Offset in A071MAIN is a positive value.

Ensure the configured DO Offset is less than the EV Offset.

Invalid embedded response enable (Y)es or (N)o

Cause:

The configured embedded response enable parameter is invalid.

Remedy:

Ensure the configured Embedded Rsp in A071MAIN is either Yes (Y) or No (N).

Invalid event timeout configured

Cause:

The configured spontaneous event timeout is invalid.

Remedy:

Ensure the configured Spontaneous Event Timeout in A071MAIN is a positive value.

Restricted

A071-0CG-2.02-2