ANSI X3.28/SRIO DPA

GE Energy Services

CONFIGURATION GUIDE

Invalid EVNT offset configured

Cause:

The configured event partition offset is invalid.

Remedy:

Ensure the configured EVNT Offset in A071MAIN is a positive value.

Ensure the configured EVNT Offset is less than the DD Offset.

Invalid EV offset configured

Cause:

The configured event storage partition offset is invalid.

Remedy:

Ensure the configured EV Offset in A071MAIN is a positive value.

Ensure the configured EV Offset is less than the AI Offset.

Invalid modem enable (Y)es or (N)o

Cause:

The configured modem enable parameter is invalid.

Remedy:

Ensure the configured Modem Enabled parameter in A071MAIN is either Yes (Y) or No (N).

Invalid Number of ENQS

Cause:

The configured number of ENQs to be re-transmitted is invalid.

Remedy:

Ensure the configured ENQ Count in A071MAIN is a positive number.

Invalid Number of NAKS

Cause:

The configured number of ENQs to be re-transmitted is invalid.

Remedy:

Ensure the configured ENQ Count in A071MAIN is a positive number.

Invalid OBJ offset configured

Cause:

The configured object partition offset is invalid.

Remedy:

Ensure the configured Obj Offset in A071MAIN is a positive value.

Ensure the configured Obj Offset is less than 27000.

A071-0CG-2.02-2Restricted

16

Full

 

Page 28
Image 28
GE A071-0CG manual Invalid Evnt offset configured, Invalid EV offset configured, Invalid modem enable Yes or No