ANSI X3.28/SRIO DPA

GE Energy Services

CONFIGURATION GUIDE

Invalid ACK time-out

Cause:

The configured ACK Timeout is invalid.

Remedy:

Ensure the configured ACK Timeout in A071MAIN is a positive value.

Invalid AI offset configured

Cause:

The configured analog input offset is invalid.

Remedy:

Ensure the configured AI Offset in A071MAIN is a positive value.

Ensure the configured AI Offset is less than the AO Offset.

Invalid Analog Format configured 32 (BIN), 6 or 3 (BCD)

Cause:

The configured Analog Formats is invalid.

Remedy:

Ensure the configured Analog Format in A071MAIN is either 32 Bit Binary (32), 6 Digit BCD (6), or 3 Digit BCD (3).

Invalid AO offset configured

Cause:

The configured analog output offset is invalid.

Remedy:

Ensure the configured AO Offset in A071MAIN is a positive value.

Ensure the configured AO Offset is less than the PD Offset.

Invalid checksum configured (B)cc or (C)rc

Cause:

The configured checksum type is invalid.

Remedy:

Ensure the configured Checksum in A071MAIN is either BCC (B) or CRC (C).

Invalid COMX configuration

Cause:

The configured port name is invalid.

Remedy:

Ensure the configured Port in A071MAIN is in the range "COM1" to "COM7".