ANSI X3.28/SRIO DPA

 

CONFIGURATION GUIDE

GE Energy Services

Mapped DI point not Found. Check config

Cause:

One of the mapped digital input points could not be located in the SPABUS configuration.

Remedy:

Ensure none of the Item Table Offsets in A071DIMP are greater than the number of records in the SPABUS item configuration table, A070ITEM.

Ensure all of the Item Table Offsets in A071DIMP refer only to records in the SPABUS item configuration table, A070ITEM, of type DI, PD, or Spare (-1).

Mapped DO point not Found. Check config

Cause:

One of the mapped digital output points could not be located in the SPABUS configuration.

Remedy:

Ensure none of the Item Table Offsets in A071DOMP are greater than the number of records in the SPABUS item configuration table, A070ITEM.

Ensure all of the Item Table Offsets in A071DOMP refer only to records in the SPABUS item configuration table, A070ITEM, of type DO or Spare (1-).

Mapped EV point not Found. Check config

Cause:

One of the mapped event data points could not be located in the SPABUS configuration.

Remedy:

Ensure none of the Item Table Offsets in A071EVMP are greater than the number of records in the SPABUS item configuration table, A070ITEM.

Ensure all of the Item Table Offsets in A071EVMP refer only to records in the SPABUS item configuration table, A070ITEM, of type EV or Spare (-1).

Missing Configuration ... Deleting

Cause:

The system was unable to locate the main configuration table for the ANSI X3.28/SRIO DPA.

Remedy:

Ensure the main configuration table, A071MAIN, exists in the configuration and is comprised of a single record.