2-2
RUN Key - Key used for starting
operation. The LED (green) lights up
during operation.
This key does not function when
terminal operation control is selected.
or
STOP Key - This key is used for
stopping drive operation. When set
as follows:
operation command input is
accepted from the Keypad (RUN
and STOP keys).
When function 2 is set to 1:
Operation command input by
means of the external signal
terminal (FWD, REV). STOP key
on the keypad is active. If
selection "1" is chosen, and the
stop button is depressed while the
drive is running, the drive will
perform the normal stop
sequence until the output
frequency reaches zero at which
point an "Er6" fault shall be
indicated on the LED. To reset the
drive you must remove the RUN
command and press RESET.
When function 2 is set to 2:
operation command input is
accepted by means of the
external signal terminal (FWD,
REV). STOP key on the keypad
is inactive.
UP / DOWN Keys - These keys
increase or decrease the
frequency reference. When unit is
in program setting mode, they
change the Function Code or data
values.
Unit Display - Unit information is
displayed by the LED (red). All
three LEDs flash to indicate that
the unit is in the program mode.
Operation Mode Indicator -
The LED (green) lights up when
keypad panel operation is
selected.
Drive RUN Indicator -
The LED (green) lights up in the
RUN mode.
(1) Keypad Part Names and Functions
Digital Display (4 digits) -
Displays the various Function
Codes and data values during
setting of the program. During
operation, it displays the output
frequency, current, voltage, etc.
If a fault occurs the cause of the
problem will be displayed as a
code.
PROGRAM Key (Reset Key) -
Normal mode or program setting
mode select key. When any of
the protection functions are
activated; this key is used to reset
the fault.
FUNCTION Key (Data Key) -
During the normal mode, this key
can be used to change the display
unit while operation is either
stopped or running.
During the program mode, this
key can be used to read and write
the Function Codes and the data.
Unit Display
Digital Display
STOP Key
Operation Mode Indicator
Program/Reset Key
Function Key (Data Key)
DOWN Key
RUN Key
UP Key
Program Mode Drive RUN Indicator
F 0 2 = 1
F 0 2 = 2
F 0 2 = 1
F 0 2 = 2
F 0 2 = 0