LED
Data Factory Customer
Display Setting Description Setting Setting
6-19
Setting range Setting step Unit
0.00 to 99.99 0.01
100.0 to 400.0 0.1
Hz
F_54 Y1 TERMINAL FUNCTION 0
(Function Selection)
This selects the output signal for the Y1 terminal from
the following 6 types:
0: Drive running state (RUN)
1: Frequency level detection (FDT)
Y1-CM is ON when the frequency detected is
identical to the frequency set by function F_55.
The hysteresis is set by function F_56.
2: Frequency equivalence signal (FAR)
Y1-CM is ON when the frequency reaches the frequency
set by the keypad panel, analog input, multistep
frequency setting etc.
The hysteresis is set by function F_56.
3: Under-voltage stop mode (LV)
4: Torque limiting mode (TL)
5: Auto-restart mode after momentary input power failure (IP)
*F_55 0.00 to 400.0 FREQUENCY LEVEL DETECTION 0.00 Hz
(FDT Operation Level)
This sets the operation level for frequency detection signal
(FDT) output within the range of 0.00 through
400.0 Hz (depends on F_03 setting). F_54 = 1
Setting resolution: