6-22
LED
Data Factory Customer
Display Setting Description Setting Setting
*F_65 1 TORQUE BOOST 2 13
2This sets the torque boost 2 to one of 31 patterns when
3 terminal X4 has been set to function as a command input
to terminal for switching to base frequency 2 (F_43 = 2).
31 Setting details are the same as for function F_08.
NOTE: For manual torque boost only; no pattern can be
selected for automatic torque boost.
F_66 See F_15 ELECTRONIC OVERLOAD 2 0
(Operation Selection)
F_67 See F_16 ELECTRONIC OVERLOAD 2 Rated motor
Current
(Operation Level) (Std. 4
When terminal X4 has been set to function as a Pole
command input terminal for switching to base frequency 2 Motor)
(F_43 = 2), this sets the electronic overload
to 2 (motor overload detection) for the second motor
to active or inactive, and also sets the operation pattern
and the operation level.
Setting details are the same as for function F_15 and F_16.
NOTE: Base frequency 2, torque boost 2 and electronic
overload 2 are only active when the X4
terminal function has been set to F_43 = 2 and
X4-CM is ON/CLOSED.
*F_68 0.0 to 5.0 SLIP COMPENSATION 0.0 Hz
Functions to suppress fluctuations in the motor speed
which result from variations in the load torque.
The slip frequency with respect to the base frequency
during rated load output (100%) can be set within the
range of 0.0 to 5.0 Hz in steps of 0.1 Hz.
If the slip compensation value is set to 0.0 Hz, then the
slip compensation function will be inactive.