F_28 S-CURVE ACCELERATION/DECELERATION 0
(Operation Selection)
Selects whether S-curve acceleration/deceleration
is active or inactive and which of the two S-curve
patterns is used.
0: Inactive - linear acceleration and deceleration (Fig. 1)
1: S-curve acceleration/deceleration (weak) Fig.2
2: S-curve acceleration/deceleration (strong) Fig. 3
NOTE:
Shocks at the start and end of acceleration and
deceleration can be softened by selecting a S-curve
pattern.
The maximum gradient in the output frequency
when a S-curve pattern is selected is the same as
for linear acceleration and deceleration time.
The actual acceleration and deceleration times when
a S-curve pattern is selected is extended by 10%
(when 1 is set) or 20% (when 2 is set) from the times
set by F_06 and F_07 or by F_63* and F_64*.
* Alternate acceleration (F_63) and deceleration (F_64)
times are selected when the terminal X4 function is set so
that F_43 = 0 and X4-CM is ON/CLOSED.