6-10

LED
Data Factory Customer
Display Setting Description Setting Setting
*F_21 MULTISTEP FREQUENCY #1 5.00Hz
*F_22 MULTISTEP FREQUENCY #2 10.00Hz
*F_23 MULTISTEP FREQUENCY #3 20.00Hz
*F_24 MULTISTEP FREQUENCY #4 30.00Hz
*F_25 MULTISTEP FREQUENCY #5 40.00Hz
*F_26 MULTISTEP FREQUENCY #6 50.00Hz
*F_27 MULTISTEP FREQUENCY #7 60.00Hz
These Functions set the frequency for multistep
frequency operation. The frequencies are selected as
shown in the table below by setting control terminals
X1-CM, X2-CM and X3-CM to ON/CLOSED.
[Relationship between terminals and multistep
frequencies 1-7] = ON/CLOSED
(1) Speed 0 (when X1-CM, X2-CM and X3-CM are all
OFF/OPEN) depends on the frequency setting method
selected by means of function F_01. In other words, the
setting becomes digital (using the and keys) or
analog ([0 to 10VDC] or [4 to 20mA VDC]).
(2) The actual operation frequency is limited by the maximum
frequency F_03 and the frequency limiters F_36 and F_37.
Function 1 21 22 23 24 2 5 26 27
Multistep
Speed Speed Speed Speed Speed Speed Speed Speed
Frequency 01234567
X1 – CM
••••
X2 – CM
•• ••
X3 – CM
••••