6-4
LED
Data Factory Customer
Display Setting Description Setting Setting
F_05 80 MAXIMUM OUTPUT VOLTAGE 230
to This sets the maximum output voltage for the
230/240 Drive in steps of 1V (230V/240V) and 2V (480V).
160
to
480 460
NOTE: The output voltage cannot be higher than the
voltage input from the power supply.
*F_06 ACCELERATION TIME 1 6.0
*F_07 DECELERATION TIME 1 6.0
0.01 The time from start to maximum frequency
to (acceleration) and from maximum frequency to stop
3600 (deceleration) can be set within the range of 0.01
to 3600 seconds. Set values according to the load
characteristics for Wk2.
*F_ 08 TORQUE BOOST 1 2
Torque boost can be set to optimize the V/Hz
characteristics of the Drive according to the type of
load the motor will see. Set only high enough to
develop sufficient low frequency torque; too high of a
value will cause diminished performance and
excessive motor heating.
0 Torque boost is automatically controlled.
1 Squared torque characteristics
(for fans and pumps)
2 Proportional torque characteristics
3 (Weak)
31 (Strong)
240V is for single phase input only.
Setting Range Setting Step
0.00* to 9.99s 0.01s
10.0 to 99.9s 0.1s

* When set to 0.00

100 to 999s 1s

the time becomes

1,000 to 3,600s 10s

0.01 seconds.