6-8

LED
Data Factory Customer
Display Setting Description Setting Setting
or more
F_15 Electronic Overload operation
(cont'd) characteristics
11) For a standard 4-pole motor
22) For a special design motor
F_16 0.01 ELECTRONIC OVERLOAD LEVEL Rated
to The level for the electronic overload protection Current (A)
99.9 algorithm (see Function Code 15) can be adjusted (Std. 4-Pole Motor)
from the factory default setting of rated Drive nameplate
amps. The setting range is approximately 20 to 105%
of rated Drive current.