6-12
LED
Data Factory Customer
Display Setting Description Setting Setting
V
Contents of the
last trip are
displayed.
Contents of the
second-last trip
are displayed.
Contents of the
third-last trip
are displayed.
Contents of the
fourth-last trip
are displayed.
This example
shows there is no
trip history for this.
*F_29 PROTECTION HISTORY/FAULT MEMORY – –
The Last 4 drive faults are displayed in order
when the key is pressed.
Operation Procedure
F_30 0 to 1 5 STARTING FREQUENCY 1 Hz
This sets the starting frequency within the range of 0 to
15Hz in 1Hz steps.
If the data is set to 0, the frequency will be 0.2Hz.
*F_31 TORQUE LIMIT 0
(During Acceleration/Deceleration)
Sets the Torque Limit level during acceleration/
deceleration in steps of 1%.
0No limit
20 20%
to Limit
180 180%
*F_32 TORQUE LIMIT 0
(At Constant Speed)
This sets the torque limit level during constant speed
operation in steps of 1%.
0No limit
20 20%
to Limit
180 180%
If the torque limit function has been selected, the Drive may
start running with differences in the acceleration/deceleration
time and speed settings. Make sure that the system is set up
properly so that there will be no danger to personnel when the
Drive starts, otherwise accidents may occur.