F_43 X4 TERMINAL FUNCTION 0
The function for the X4 input terminal can be selected from
the following four options.
0: Functions as a command input terminal X4 for
switching to acceleration/deceleration time 2.
The acceleration time 2 and deceleration time 2 are set
by F_63 and F_64.
1: Enables the use of multistep frequency settings 8 to 15.
Frequencies 8 to 15 are set by means of F_44 to F_51.
2: Functions as a command terminal X4 for switching
to base frequency 2 when using a second motor, etc.
When base frequency 2 is selected, acceleration/
deceleration time 2, torque boost 2 and electronic
overload 2 are selected simultaneously.
Base frequency 2 is set using function F_62, acceleration/
deceleration time 2 are set by function F_63 and F_64,
torque boost 2 is set by function F_65, and electronic
overload 2 is set by F_66 and F_67.
3: Functions as a hold signal (HLD) for operation commands
during 3-wire control operation.
*F_44 MULTISTEP FREQUENCY SETTING 8 0.00
*F_45 MULTISTEP FREQUENCY SETTING 9 0.00
*F_46 MULTISTEP FREQUENCY SETTING 10 0.00
*F_47 0 to 40 0 MULTISTEP FREQUENCY SETTING 11 0.00
*F_48 MULTISTEP FREQUENCY SETTING 12 0.00
*F_49 MULTISTEP FREQUENCY SETTING 13 0.00
*F_50 MULTISTEP FREQUENCY SETTING 14 0.00
*F_51 MULTISTEP FREQUENCY SETTING 15 0.00
These set the 8 multistep frequencies from frequency 8 to
frequency 15 within the range of 0 to 400Hz.
The setting step is the same as for functions F_21 through
F_27.
(Relationship between terminals and multistep frequencies
8 through 15) • = ON/CLOSED.
NOTE: These functions are only active when F_43 = 1 (X4).
Function 44 45 46 47 48 49 5 0 51
Multistep
Speed Speed Speed Speed Speed Speed Speed Speed
Frequency 8 9 10 11 12 13 14 15
X1 – CM
••••X2 – CM
•• ••X3 – CM
••••X4 – CM
••••••••