Display Setting Description Setting Setting
6-23
F_69 TORQUE VECTOR CONTROL 0
This selects whether Torque Vector Control is active
or not.
0: Torque Vector Control inactive
1: Torque Vector Control active
NOTE: Torque Vector Control does not function if
is selected when the X4 terminal function has been set
to (F_43 = 2) and X4-CM is ON/CLOSED. The manual
torque boost selected by F_65 will apply.
NOTE: For best results perform Auto Tuning Function
(F_74) prior to activation of Torque Vector Control.
F_70 MOTOR HP CAPACITY 1
This sets the HP capacity of the motor which is connected
in relation to the Drive capacity.
0: 1-frame up capacity for standard applied motor
1: Standard capacity for standard applied motor
2: 1-frame down capacity for standard applied motor
3: 2-frame down capacity for standard applied motor
F_71 0.00 MOTOR 1 RATED CURRENT 4-pole
F_72 to MOTOR 1 NO-LOAD CURRENT 4-pole
99.9 These set the rated current (A) and no-load current (A) (Std.
for the motor which is connected to the Drive. Design B)
EXPLANATION: The primary resistance (R1) and
leakage reactance (X1) are automatically rewritten
with the rated value of the motor capacity (F_70),
motor 1rated current F_71 and motor 1no-load
current (F_72) are set.
F_73 0.00 MOTOR 2 RATED CURRENT Rated
to This sets the rated current (A) for the second motor which Current
99.9 is selected when base frequency 2 (F_62) is active. (Std. 4-Pole
Motor)