4-4
Table 4: Wire Size Recommendations& Circuit Protection Ratings240V – Single Phase and 230V Three Phase
DB Incoming Power
Model PH HP Output Current Power Resistor** AC – Line Devices
NEMA 1 NEMA 4
Const
Carrier Frequency
Wire Wire Circuit
Input TRQ Low High AWG AWG Fuses* Breaker
6KM$221F25N1A1 6KM$221F25X4A1 1 1/4 1.5 1.3 16 - 6 5
6KM$221F50N1A1 6KM$221F50X4A1 1 1/2 3 2.5 16 16 10 10
6KM$221001N1A1 6KM$221001X4A1 1 1 5 4 14 14 15 15
6KM$221002N1A1 6KM$221002X4A1 1 2 8 7 12 12 20 20
6KM$221003N1A1 6KM$221003X4A1 1 3 11 10 10 10 30 30
6KM$223F25N1A1 6KM$223F25X4A1 3 1/4 1.5 1.3 16 - 6 5
6KM$223F50N1A1 6KM$223F50X4A1 3 1/2 3 2.5 16 16 10 5
6KM$223001N1A1 6KM$223001X4A1 3 1 5 4 16 16 15 10
6KM$223002N1A1 6KM$223002X4A1 3 2 8 7 14 14 20 15
6KM$223003N1A1 6KM$223003X4A1 3 3 11 10 14 14 30 20
6KM$223005N1A1 6KM$223005X4A1 3 5 17 16.5 10 10 40 30
480V – Three Phase
DB Incoming Power
Model PH HP Output Current Power Resistor** AC – Line Devices
NEMA 1 NEMA 4
Const
Carrier Frequency
Wire Wire Circuit
Input TRQ Low High AWG AWG Fuses* Breaker
6KM$243F50N1A1 6KM$243F50X4A1 3 1/2 1.6 1.4 16 14 6 5
6KM$243001N1A1 6KM$243001X4A1 3 1 2.5 2.1 16 14 6 5
6KM$243002N1A1 6KM$243002X4A1 3 2 3.7 3.7 16 14 15 10
6KM$243003N1A1 6KM$243003X4A1 3 3 5.5 5.3 16 14 15 15
6KM$243005N1A1 6KM$243005X4A1 3 5 9.0 8.7 14 14 20 15
WARNING - Device ratin
g
s such as s
y
stem coordination, short-circuit
rat
i
n
g
an
d
t
yp
e must
b
e care
f
u
lly
rev
i
ewe
d
by
t
h
e user.
NOTE:
Wire size from NEC table 310-16. Copper wire rated 60° C for 100 amps or less,
75° C for over 100 amps in 30° C ambient and 1.25 times Drive rated amps. These
are minimum wire sizes; consult and conform to local and national codes.
*NOTE: AC input fuses are required to validate the drive's UL and CSA approvals.
The fuse should be Class J type such as Bussman, JKS or equivalent. Circuit breaker
ratings are shown for reference, but UL and CSA approval can only be validated by
the use of Class J fuses.
** Optional Item.