SECTION 5. INSTALLING THE TRIP UNIT

1.Remove the large screw from the rear of the trip unit. Place the trip unit in position on the mount- ing plate, with the 50-pin connector aligned with the opening in the plate. Secure with the large screw, as shown in Figure 22.

2.Insert the 50-pin female connector on the wiring harness into the trip unit connector through the rear of the mounting plate. Secure to the mount- ing plate with the two small screws provided, as shown in Figure 22.

3.Place the trip unit and mounting plate in position on the support bracket mounted on the breaker. Secure with the three screws, lock washers, and flat washers through the holes in the mounting plate into the tapped holes in the bracket, as shown in Figure 23.

Configuring the Trip Unit

See DEH-40034 for detailed instructions for setting up ProTrip trip units.

Trip Unit

Mounting

Plate

Trip

Unit

Trip Unit

Mounting

Screw

Wiring

Harness

Connector

Figure 22. Attaching the trip unit to the mounting plate.

Figure 23. Trip unit mounted on the breaker.

15

Page 15
Image 15
GE AK-50 installation instructions Installing the Trip Unit, Configuring the Trip Unit