Installing the Flux Shifter Assembly

The installation procedure for the flux shifter assembly, illustrated in Figure 3, varies depending on the type of breaker and existing trip device. In some cases, mounting holes must be added, termi- nal blocks relocated, or breaker side rails removed.

Breakers with EC or Power Sensor Trip Systems

1.Drill the flux shifter mounting holes in the left side of the breaker frame. The mounting hole pattern is illustrated in Figure 4. A full-size tem- plate is provided in the Appendix.

2.Mount the new flux shifter to the inside of the side frame with the three screws, lock washers, flat washers, and nuts supplied, as shown in Figure 5. Insert the screws from the outside of the side frame.

Figure 4. Pattern for flux shifter mounting holes in the side frame.

Mounting

 

 

Screws

 

 

Flux Shifter

 

 

 

 

 

 

Assembly

 

 

 

Figure 5. Flux shifter assembly mounted to the side frame.

Figure 3. Flux shifter assembly.

6

Page 6
Image 6
GE AK-50 installation instructions Installing the Flux Shifter Assembly, Breakers with EC or Power Sensor Trip Systems