PRODUCT DESCRIPTION

2.4.TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE

 

2.4.1.

INPUTS

Activation range:

Programmable from 1 up to 255 Vdc in steps of 1 V

 

Impedance

> 100 kOhm

 

Load for voltage supervision inputs

2 mA + V/100 kOhm

 

Acknowledgement time

<1 m

 

Debounce time:

1 to 50 ms in steps of 1 ms

 

 

 

2.4.2.

OUTPUTS

Permanent current

16

A

 

Closing current

60

A during 1 second

 

Opening current

0.3 A with L/R = 40 ms at 125 Vdc

 

 

0.25 A with L/R = 40 ms at 250 Vdc

 

 

 

2.4.3.

CONTROL POWER SUPPLY

LO (low range)

 

 

 

Range:

24 to 48 Vdc (from 24 Vdc – 15% to 48 Vdc + 20%)

HI (high range)

 

 

 

Range:

110 to 250

Vdc (from 110 Vdc – 15% to 250 Vdc + 20%)

 

110 to 240

Vac (from 110 Vac – 15% to 240 Vac + 20%)

Consumption:

5 W typical

 

 

 

0.25 W more per each activated output.

Interruptions:

Typical 100 ms, without unit reset.

 

 

2.4.4.

CAN BUS

Baudrate:

125 kbits per second

 

Media:

Glass fiber optic multimode with ST connectors.

 

 

Maximum recommended length 1Km

 

 

3 wire cable connection

 

 

Maximum recommended length 500m

 

 

2.4.5.

ENVIRONMENTAL CHARACTERISTICS

Operation temperature:

- 10°C to + 60°C

 

Storage temperature:

- 40°C to + 80°C

 

Humidity:

95% without condensing.

GEK-106465A

CIO Remote CAN Digital I/O Module

11

Page 12
Image 12
GE GEK-106465A instruction manual Technical Specifications