I/O MODULES DESCRIPTION
5.2.CONTROL SETTINGS FOR INPUTS/OUTPUTS
This section explains the settings related to CIO inputs/outputs. Modification of these values is performed using the master unit communication software, EnerVista F650Setup for F650, or
5.2.1. INPUT/OUTPUT BOARDS SETTINGS
Settings relative to I/O boards are described in table
TABLE
| SETTING |
|
| HMI |
| DEFAULT |
| I/O board type (available only for |
|
| I/O Board_X Type |
| NONE |
| CIO modules) |
|
|
| ||
|
|
|
|
|
|
|
| Input activation voltage threshold |
|
| Voltage Threshold A_X |
| 80 |
| Group A |
|
|
| ||
|
|
|
|
|
| |
| Input activation voltage threshold |
|
| Voltage Threshold B_X |
| 80 |
| Group B |
|
|
| ||
|
|
|
|
|
| |
|
|
|
|
|
| |
| Debounce time Group A |
| Debounce Time A_X |
| 15 | |
| Debounce time Group B |
| Debounce Time B_X |
| 15 | |
| Input type |
|
| Input Type_X_CCY |
| POSITIVE |
|
|
|
|
|
|
|
| Input signal time delay |
|
| Delay Input |
| 0 |
|
|
| Time_X_CCY |
| ||
|
|
|
|
|
| |
| Output logic type |
| Output Logic_X_0Z |
| POSITIVE | |
|
|
|
|
|
|
|
| Output type |
|
| Output Type_X_0Z |
| NORMAL |
|
|
|
|
|
|
|
| Output pulse length |
|
| Pulse Output |
| 0 |
|
|
| Time_X_0Z |
| ||
|
|
|
|
|
|
RANGE
16 INP + 8OUT
8 INP + 8OUT +
SUPV
NONE
0 – 255 V
0 – 255 V
1 – 50 ms
1 – 50 ms
0 – 60000 ms
POSITIVE-
NEGATIVE
NORMAL
PULSE
LATCH
0 – 60000 ms
STEP
N/A
1 V
1 V
1ms
1ms
N/A
1ms N/A
N/A
1 ms
Being:
XI/O board name, depending on the CIO model.
For the I/O board selection in the relay model, associated digits to each board type are as follows:
ASSOCIATED DIGIT | F650PC BOARD | BOARD TYPE |
| SETTINGS |
|
0 | NONE | None |
1 | 16 INP+ 8OUT | Mixed |
2 | 8 INP +8 OUT +SUPV | Supervision |
|
|
|
32 | CIO Remote CAN Digital I/O Module |