HARDWARE
INTERNAL STATE | V 52/a | SUPERVISION |
52 open | ON | Ok |
52 closed | ON | Ok |
TRIP | OFF | Ok if t < 0.5 s |
TRIP with 52 open | OFF | Ok if t < 0.5 s |
There is a possibility to monitor the trip circuit and trip coil continuity. This can be done by monitoring Vdc through the output contact when this is open.
As shown on FIGURE
This is the first case shown on the table. With closed breaker, voltage is detected by V 52/a sensor, and this means that there is continuity in the supervised circuit.
In this table, ON means that the voltage detector V52/a is active, detecting voltage presence.
Status of Involved Elements | Input to F650 | Decision | ||
CIRCUIT | OUTPUT | BREAKER | OPERAND | OPERAND |
STATUS | STATUS | STATUS | CONTACT | CONTACT |
|
| INPUT_00_10 | INPUT_00_15 | |
|
|
| (Va_COIL2) | (SUP_COIL2) |
|
|
| V 52/a |
|
Healthy | Open | 52 closed | ON | ON |
|
|
|
|
|
Healthy | Open | 52 open | ON | ON |
Healthy | Closed | 52 closed | OFF | ON (if t < 500 ms) |
|
|
|
| OFF (if t > 500 ms) |
Healthy | Closed | 52 open | OFF | ON (if t < 500 ms) |
|
|
|
| OFF (if t > 500 ms) |
Faulty | Open | 52 closed | OFF | OFF (500 ms delay) |
|
|
|
|
|
Faulty | Open | 52 open | OFF | OFF (500 ms delay) |
Faulty | Closed | 52 closed | OFF | OFF (500 ms delay) |
Faulty | Closed | 52 open | OFF | OFF (500 ms delay) |
|
|
|
|
|
24 | CIO Remote CAN Digital I/O Module |