GE GEK-106465A instruction manual Internal State, Circuit Output Breaker Operand Status

Models: GEK-106465A

1 43
Download 43 pages 35.58 Kb
Page 25
Image 25

HARDWARE

INTERNAL STATE

V 52/a

SUPERVISION

52 open

ON

Ok

52 closed

ON

Ok

TRIP

OFF

Ok if t < 0.5 s

TRIP with 52 open

OFF

Ok if t < 0.5 s

There is a possibility to monitor the trip circuit and trip coil continuity. This can be done by monitoring Vdc through the output contact when this is open.

As shown on FIGURE 3-10, when the relay is not tripped, trip contact 35-36 remains open. If the breaker is closed, its auxiliary contact 52a is closed. Therefore, a little current is flowing, about 2 mA, through terminals 15 and 16 through the voltage detector circuit, which flows through 52/a and the tripping coil 52TC (TC = tripping coil). Current will only circulate when there is continuity in the whole circuit, so the complete circuit is monitored, and not only the trip coil. This circuit includes auxiliary 52/a as well as the whole wiring between the battery and the relay tripping terminals, and between these and the breaker tripping circuit.

This is the first case shown on the table. With closed breaker, voltage is detected by V 52/a sensor, and this means that there is continuity in the supervised circuit.

In this table, ON means that the voltage detector V52/a is active, detecting voltage presence.

Status of Involved Elements

Input to F650

Decision

CIRCUIT

OUTPUT

BREAKER

OPERAND

OPERAND

STATUS

STATUS

STATUS

CONTACT

CONTACT

 

(F35-F36)

 

INPUT_00_10

INPUT_00_15

 

 

 

(Va_COIL2)

(SUP_COIL2)

 

 

 

V 52/a (F15-F16)

 

Healthy

Open

52 closed

ON

ON

 

 

 

 

 

Healthy

Open

52 open

ON

ON

Healthy

Closed

52 closed

OFF

ON (if t < 500 ms)

 

 

 

 

OFF (if t > 500 ms)

Healthy

Closed

52 open

OFF

ON (if t < 500 ms)

 

 

 

 

OFF (if t > 500 ms)

Faulty

Open

52 closed

OFF

OFF (500 ms delay)

 

 

 

 

 

Faulty

Open

52 open

OFF

OFF (500 ms delay)

Faulty

Closed

52 closed

OFF

OFF (500 ms delay)

Faulty

Closed

52 open

OFF

OFF (500 ms delay)

 

 

 

 

 

24

CIO Remote CAN Digital I/O Module

GEK-106465A

Page 25
Image 25
GE GEK-106465A instruction manual Internal State, Circuit Output Breaker Operand Status