The following lines describe the different types of connection to create each scheme in an easy way. As the supervision circuits are identical, we will describe connection examples for the first group. They are also applicable to the second group.

The symmetrical location of digital inputs is an optimization for ensuring a high isolation between groups that, belonging to different groups could be connected to separate batteries, and therefore a greater distance between circuits is required.

3.4.2.1. WITHOUT SUPERVISION

This is a very frequent case, and we must only wire the tripping circuit to terminals 35 and 36, leaving unused terminals 34, 15, 16, 17, 18.

FIGURE 3-8 CIRCUIT WITHOUT TRIPPING CIRCUIT SUPERVISION (A6631F1)

GEK-106465A

CIO Remote CAN Digital I/O Module