HARDWARE

INTERNAL STATE

V 52/a

V 52/b

SUPERVISION

52 open

ON

ON

OK

52 closed

ON

OFF

OK

TRIP

OFF

OFF

Ok if t < 0.5 s

TRIP with 52 open

OFF

ON

OK

Status of Involved Elements

Inputs to F650

 

CIRCUIT

OUTPUT

BREAKER

OPERAND

 

OPERAND

 

STATUS

STATUS

STATUS

CONTACT

 

CONTACT

 

 

(F35-F36)

 

INPUT_00_10

 

INPUT_00_11

 

 

 

 

(Va_COIL2)

 

(Vb_COIL2)

 

 

 

 

V 52/a (15-16)

 

V 52/b (17-18)

 

Healthy

Open

52 closed

ON

 

OFF

 

Healthy

Open

52 open

ON

 

ON

 

Healthy

Closed

52 closed

OFF

 

OFF

 

 

 

 

 

 

 

 

Healthy

Closed

52 open

OFF

 

ON

 

 

 

 

 

 

 

 

Defective

Open

52 closed

OFF

 

OFF

 

Defective

Open

52 open

OFF

 

OFF

 

Defective

Closed

52 closed

OFF

 

OFF

 

 

 

 

 

 

 

 

Defective

Closed

52 open

OFF

 

OFF

 

Decision

OPERAND CONTACT INPUT_00_15 (SUP_COIL2)

ON

ON

ON (if t < 500 ms) OFF (if t > 500 ms)

ON (if t < 500 ms) OFF (if t > 500 ms)

OFF (500 ms delay)

OFF (500 ms delay)

OFF (500 ms delay)

OFF (500 ms delay)

There is a possibility to monitor the trip circuit continuity not only via its auxiliary contact 52/a, but also with auxiliary contact 52/b. This avoids the need to install a resistance in parallel with auxiliary 52/a. The correct connection is shown on FIGURE 3-12.

The circuit works in a similar way to the one described in the previous section, but it uses both supervision inputs 15- 16 and 17-18.

The advantage in this case is that circuit supervision with 52 open is more complete, as input V 52/b is used through contact 52/b, (that is closed when the breaker is open).

We must point out that in this scheme, the tripping contact, shown in the example as the CIO trip relay, can be the one in the relay (terminals 35 and 36), or be provided by another protection or by the parallel of several protections. This provides high flexibility in the use of this circuit.

The battery voltage can also be monitored, by using one of the standard digital inputs.

28

CIO Remote CAN Digital I/O Module

GEK-106465A

Page 29
Image 29
GE GEK-106465A instruction manual 52/a 52/b, Status of Involved Elements Inputs to F650, Operand Contact INPUT0015 SUPCOIL2