8.5CAN Wiring Rules
| L | IE L D | H |
|
| L | IE L D | H |
| L | IE L D | H |
|
V- | C N | S H | C N | V + | V- | C N | S H | C N | V + | V- C N | S H | C N | V + |
1 2 1 Ω
+
1 2
-
L | IE L D | H |
|
V- C N | S H | C N | V + |
1 2 1 Ω
| L | IE L D | H |
|
| L | IE L D | H |
|
| L | IE L D | H |
|
| L | IE L D | H |
|
V - | C N | S H | C N | V + | V - | C N | S H | C N | V + | V - | C N | S H | C N | V + | V - | C N | S H | C N | V + |
B L K | B L U 1 2 1 Ω | W H T | R E D H IE L D |
|
|
| S |
-
+
1 2
B L K | B L K |
|
| Ω |
|
|
|
| LK | LU | 1 | HT | ED |
B L U | B L U | 1 2 | ||||
|
|
|
|
| ||
W H T | W H T | B | B |
| W | R |
|
|
|
|
| ||
R E D | R E D |
|
|
|
|
|
S H IE LD | S H IE LD |
Figure 8.3 – CAN Network Cabling
1.Wire the CAN network in a
2.The two nodes at the physical
3.Use data conductors (CN_L and CN_H) that are 24 AWG shielded twisted pair for “thin cable” and 22 AWG shielded twisted pair for “thick cable”. They must also have
4.Use power conductors (V- and V+) that are 18 AWG
5.Connect the V- power conductor to a good earth ground at one place only on the network, preferably physical endpoints.
6.For a section of cable between two nodes, the cable shield is connected to the cable shield input at one end of the cable only.
7.A CAN network (without repeaters) is limited to 64 nodes (with 63 cable segments) with a maximum cable length of 1500 ft.
8.Up to four CAN network segments, which adhere to the above rules, may be connected together using three CAN repeaters. In this manner, a CAN network may be extended to 253 nodes with a total cable distance of 6000 ft.