CH. 8: NETWORKS

06 Apr 2000

PAGE 41

 

 

GFK-1819

8.6Profibus

Profibus utilises a Master-Slave type of communication with the TIUXX2 functioning as a slave device. Decentralised Peripherals (Slave) Baud rates of up to 12 MBd can be obtained through Profibus.

Up to 32 devices 9master or slaves) can be connected in one segment without using repeaters, or up to 64 devices can be connected using repeaters.

Master devices are used to determine the data communication on the bus. One master can service several slaves. Several Masters can participate on the bus simultaneously, but only one Master can write outputs to a slave.

The slave devices are peripheral devices. Slaves do not have bus access rights and can only acknowledge received messages or send messages to the master when requested to do so. Any master can read data from the slave devices. All connected Slaves have the same priority.

For further information on the Profibus Network, visit their website at www.profibus.com

8.6.1Profibus Wiring

The TIUXX2 uses a 9 pin D-sub plug connector for its Profibus port. The pin assignment of the plug connector and the wiring are show below.

Station 1

Station 2

R xd/TxD -P 3 3

V + 6

6

D G nd 5

5

R xD /TxD -N 8 8

P rotective G round

Figure 8.4 Profibus Port Pinout

Page 40
Image 40
GE IC300TIU101, IC300TIU201, HE500TIU100, HE500TIU050, HE500TIU113, HE500TIU202 manual Apr GFK-1819 Profibus, Profibus Wiring