Section 2 – Installation

Recreational Vehicle Generator

The greater the airflow through the carburetor ven- turi, the lower the pressure at the venturi throat. The lower the pressure at the venturi throat, the greater the diaphragm movement, and the greater the move- ment of the regulator valve. The more the regulator valve opens, the greater the gas flow that is propor- tional to airflow through the generator.

The following facts about the secondary regulator must be emphasized:

The regulator must be sensitive to venturi throat pressure changes throughout the operating range.

The regulator must be properly adjusted so it will stop the flow of gas when the engine is not running (no air flow through the carburetor).

The slightest airflow (and vacuum in the venturi throat) should move the regulator valve off its seat and permit gas to flow.

‹2.4.6 FUEL SUPPLY LINES

LP gas lines must be accessible, but protected against possible damage.

Do NOT connect electrical wiring to any LP gas fuel line or run wiring alongside the lines.

Route gas lines away from hot engine exhausts.

Retain gas lines with metal clamps that do not have sharp edges.

Install an approved length of flexible hose between the gaseous fuel solenoid valve and rigid fuel supply lines. The flexible line must be nonmetal- lic, nonorganic and nonconductive. It must be approved for use with LP gas.

‹2.4.7 EXCESS FLOW VALVE

LP gas tanks should have an excess flow valve, according to NFPA 501C, Paragraph 3-4.4. This valve and the gas lines must be carefully sized so the valve will close when a fuel line is severed or broken. Consult the Natural-LP Gas Association for informa- tion and limitations of excess flow valves.

Manual shutoff valves on the supply tank and else- where in the system must be fully open when oper- ating the generator. The excess flow valve functions properly only if all valves are fully open.

‹2.4.8 LEAKAGE TESTS

Do not place the generator into service until the gas system has been properly tested for leaks. To test the system, a separate source of 12 volts DC is needed to open the gaseous fuel solenoid valve.

The leak test must comply fully with NFPA, Paragraph

318.All connections, hoses, valve regulators, fittings, and other fuel system parts must be tested under gas or air pressure of not less than 90 psi (620 kPa), while using soap and water or an equivalent solution to check for leaks. Other approved methods of testing for leaks may be used, if appropriate. DO NOT USE ANY FLAME TO TEST FOR LEAKS.

DANGER

Gaseous fuel lines between the tank and the secondary regulator are under a positive pres- sure (about 11 inches water column). Gas pres- sure at the outlet side of the secondary regula- tor, however, is a negative pressure and can draw flame inside a line or fitting and cause an explosion.

2.5EXHAUST SYSTEM

The generator exhaust system must be safely and properly installed. Only approved mufflers and other exhaust system parts must be used. A properly installed exhaust system must be vapor tight, quiet and completely safe.

DANGER

The generator engine gives off DEADLY carbon monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient con- centrations, can cause unconsciousness or even death. Never operate the generator set with the vehicle inside any garage or other enclosed area. DO NOT OPERATE THE GENERATOR IF THE EXHAUST SYSTEM IS LEAKING OR HAS BEEN DAMAGED. SYMPTOMS OF CARBON MONOXIDE POISONING ARE (a) inability to think coher- ently; (b) vomiting; (c) twitching muscles; (d) throbbing temples; (e) dizziness; (f) headaches;

(g) weakness; and (h) sleepiness. IF FEELING ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET MEDICAL HELP. Do not operate the generator until its exhaust system has been inspected and properly repaired.

Never tee the generator engine exhaust pipe into the vehicle engine exhaust piping. This causes excessive back pressure on the generator engine. Also, water from one engine can dam- age the other engine.

28

Page 30
Image 30
Generac Power Systems 004701-0 Exhaust System, ‹ 2.4.6 Fuel Supply Lines, ‹ 2.4.7 Excess Flow Valve, ‹ 2.4.8 Leakage Tests

004701-0 specifications

Generac Power Systems has established itself as a leading provider of backup power solutions, and one of its standout products is the Generac 004701-0. Renowned for its reliability and advanced features, this model is designed to meet the growing demand for dependable power in residential and commercial applications.

At the heart of the Generac 004701-0 is its robust engine, which offers outstanding performance and efficiency. The unit is powered by a Generac 999cc V-Twin engine, specifically crafted to deliver reliable power during outages. This powerful engine ensures a significant output of up to 22,000 watts, making it suitable for larger homes or businesses that require more energy-intensive appliances to remain operational during outages.

One of the most notable features of the 004701-0 is its innovative True Power Technology. This technology provides clean and stable power, which is essential for sensitive electronics. Unlike some generators that produce a fluctuating output, Generac's True Power Technology ensures that the voltage remains consistent, preventing damage to your appliances.

Another key characteristic of the Generac 004701-0 is its user-friendly controls. The unit comes equipped with a comprehensive LED display that provides vital information at a glance, such as runtime hours and maintenance intervals. This feature ensures users can monitor their unit effectively and keep it in optimal condition.

The generator also boasts an advanced communication system that allows for remote monitoring. With the Generac Mobile Link app, users can check real-time status updates, monitor power usage, and receive alerts directly on their smartphone or tablet. This level of connectivity adds convenience and peace of mind, as users can stay informed about their power systems from anywhere.

Built with durability in mind, the 004701-0 features a corrosion-resistant enclosure that can withstand various environmental conditions. Its weather-resistant design makes it suitable for outdoor installation, ensuring that it remains operational when most needed.

The Generac 004701-0 is also designed with user safety in mind. It incorporates several safety features, including a low-oil shutdown and high-temperature shutdown, which help protect the engine from potential risks. This commitment to safety, combined with its powerful performance and advanced technology, makes the 004701-0 an exceptional choice for anyone looking for a dependable backup power solution.

Whether you're facing a storm, a power grid failure, or simply need reliable power for everyday use, the Generac 004701-0 stands ready to deliver, ensuring that you and your loved ones stay safe and comfortable.