Section 2 – Operation

Recreational Vehicle Generator

To start the generator from either the generator con- trol panel or from the optional remote panel, proceed as follows:

1.Turn OFF electrical loads using the means pro- vided in the vehicle (such as a main line circuit breaker or transfer switch).

NOTE:

If starting from the generator control panel, turn OFF loads by setting the generator’s main circuit breaker to the OFF (or open) position. If starting from a remote panel, turn OFF loads using the means provided in the vehicle (such as a main circuit breaker). Electrical load circuits will be turned ON after the generator has started, stabi- lized and warmed up.

2.If the engine has not been started in more than two weeks, press the Fuel Pump Primer switch and hold it for about 10 to 15 seconds to prime the fuel system. However, if the engine is warm, skip Step 2.

3.Hold the engine Start/Stop switch in the START position to crank the engine. Release the switch when the engine starts.

‹2.6.1 LETTING THE ENGINE STABILIZE

The generator supplies correct rated voltage only at the proper governed speed. Some electrical appli- ances may be extremely sensitive to voltage. Incorrect voltages can damage such appliances.

If electrical loads are applied at reduced operating speeds, such loads imposed on the engine when suf- ficient power is not available may shorten engine life. Never turn ON electrical loads until after the genera- tor engine has started and stabilized at no-load.

2.7DO NOT OVERLOAD THE

GENERATOR

Read the rated wattage/amperage capacity of the generator on the generator data label (see "Generator Identification").

Applying electrical loads in excess of the unit’s rated capacity will cause the engine/generator to automati- cally shut down.

To avoid overloading, add up the wattage of all con- nected electrical lighting, appliance, tool and motor loads. This total should not be greater than the generator’s rated wattage capacity.

If the engine does not start after it has been cranking for 15 seconds, release the Start/Stop switch, wait one minute and try again. Holding the switch for longer than 15 seconds can dam- age the starter motor.

4.Let the engine run at no-load for a few minutes to stabilize and warm up.

5.Turn ON electrical loads using the means pro- vided (such as a main circuit breaker or transfer switch).

2.5STOPPING THE GENERATOR

1.Turn OFF all electrical loads using the means provided (such as a main circuit breaker or transfer switch).

2.Let generator run at no-load for a few minutes, to stabilize internal engine generator temperatures.

3.Place the Start/Stop switch in its STOP position.

Most lighting, appliance, tool and motor loads indicate their required watts on their nameplate or data plate. For light bulbs, simply note the wattage rating of the bulb.

If a load does not show its rated wattage, multiply that load’s rated VOLTS times AMPS to obtain

WATTS.

Induction type motors (such as those that run the vehicle’s furnace fan, refrigerator, air conditioner, etc.) need about 2-1/2 time more watts of power for starting than for running (for a few seconds during motor starting). Be sure to allow for this when con- necting electrical loads to the generator. First, fig- ure the watts needed to start electric motors in the system. To that figure, add the running wattages of other items that will be operated by the generator.

Do not apply heavy electrical loads for the first two or three hours of operation.

2.6APPLYING LOADS TO GENERATOR

When applying electrical loads to the generator, observe these guidelines:

Before applying electrical loads, let the generator stabilize and warm up for a minute or two.

DO NOT overload the generator.

2.8PROTECTION SYSTEMS

‹2.8.1 LOW OIL PRESSURE SWITCH

This switch (Figure 2.2) has normally closed (N.C.) contacts that are held open by engine oil pressure dur- ing cranking and operating. Should oil pressure drop below a preset level, switch contacts close, and the engine automatically shuts down. The unit should not be restarted until oil is added.

8

Page 10
Image 10
Generac Power Systems 004701-0 owner manual Do not Overload Generator, Stopping the Generator, Protection Systems

004701-0 specifications

Generac Power Systems has established itself as a leading provider of backup power solutions, and one of its standout products is the Generac 004701-0. Renowned for its reliability and advanced features, this model is designed to meet the growing demand for dependable power in residential and commercial applications.

At the heart of the Generac 004701-0 is its robust engine, which offers outstanding performance and efficiency. The unit is powered by a Generac 999cc V-Twin engine, specifically crafted to deliver reliable power during outages. This powerful engine ensures a significant output of up to 22,000 watts, making it suitable for larger homes or businesses that require more energy-intensive appliances to remain operational during outages.

One of the most notable features of the 004701-0 is its innovative True Power Technology. This technology provides clean and stable power, which is essential for sensitive electronics. Unlike some generators that produce a fluctuating output, Generac's True Power Technology ensures that the voltage remains consistent, preventing damage to your appliances.

Another key characteristic of the Generac 004701-0 is its user-friendly controls. The unit comes equipped with a comprehensive LED display that provides vital information at a glance, such as runtime hours and maintenance intervals. This feature ensures users can monitor their unit effectively and keep it in optimal condition.

The generator also boasts an advanced communication system that allows for remote monitoring. With the Generac Mobile Link app, users can check real-time status updates, monitor power usage, and receive alerts directly on their smartphone or tablet. This level of connectivity adds convenience and peace of mind, as users can stay informed about their power systems from anywhere.

Built with durability in mind, the 004701-0 features a corrosion-resistant enclosure that can withstand various environmental conditions. Its weather-resistant design makes it suitable for outdoor installation, ensuring that it remains operational when most needed.

The Generac 004701-0 is also designed with user safety in mind. It incorporates several safety features, including a low-oil shutdown and high-temperature shutdown, which help protect the engine from potential risks. This commitment to safety, combined with its powerful performance and advanced technology, makes the 004701-0 an exceptional choice for anyone looking for a dependable backup power solution.

Whether you're facing a storm, a power grid failure, or simply need reliable power for everyday use, the Generac 004701-0 stands ready to deliver, ensuring that you and your loved ones stay safe and comfortable.