Section 3 –
Recreational Vehicle Generator
6.Turn off all electrical loads by setting the gener- ator’s main circuit breakers to their “OFF” (or open) position.
7.Let the unit run at
NOTE:
The generator set was thoroughly tested and adjusted at the factory before shipping. No addi- tional adjustment should be necessary. Only quali- fied service technicians who have been trained should perform adjustments outlined in this manual.
3.4TESTING UNDER LOAD
Apply electrical loads equal to about 75 to 100 per- cent of the unit's rated wattage/amperage capacity.
Let the unit run at least 30 minutes with load applied. During this part of the test, check that the unit is not running excessively hot and that adequate cooling airflow is available. Do not allow the unit to overheat during prolonged operation.
NOTE:
The generator engine is equipped with a high tem- perature switch. The switch has normally closed (N.C.) contacts. When the engine temperature is too high, switch contacts close, and the engine shuts down automatically.
THE MANUFACTURER RECOMMENDS THAT THE GENERATOR BE TESTED FOR ADEQUATE COOL- ING.
34