VENT EXAMPLES FOR SINGLE FLUE

Max Vent Run - 20ft. Equivalent With Three (3) 90° Elbows

Three foot (3’ (91.4cm)) minimum vent run vertical with one (1) 90° elbow

The vent terminal 90° elbow and first 90° elbow off back of heater when within 6” (15.2cm) off back of heater do not get count- ed.

Special Note: For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18” (45cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system. Reduce the length of the hori- zontal run 36” (91.4cm) for every 90° elbow.

Note: On horizontal runs, a P.V.C. support clamp needs to be installed every 3 feet. No “sags” in horizontal vent runs; water will settle in the pipe.

When installing a single flue horizontal, minimum vent length protruding from the outside wall including 90° elbow is 6” (15.2cm) from the outside wall. See Figure 14.

Note: Horizontal discharge 90° elbow must be pointed downward. See Figure 16.

Note: All PVC vent run piping can be purchased at a local hardware store. Schedule 40 PVC pipe should be used and cemented.

6” (15.2cm)

VENT TERMINAL

3’ (91.4cm) MIN.

1 - 90° ELBOW

 

2’

 

90° ELBOW

(61.0cm)

VENT TERMINAL

 

90° ELBOW

FIRST 90° ELBOW

DOES NOT GET COUNTED

WHEN WITHIN 6” (15.2cm)

OFF BACK OF HEATER

Figure 14

Single Flue - Horizontal Short Vent Run Minimum vertical vent runs is 3’ (91.4cm)

H =

5’ + 2’ = 7’

V =

7’

(2) - 90° =

6’

Total =

20’

5’

(1.5m)

7’

(2.1m)

90° ELBOW

Figure 15

Single Flue - Unacceptable Venting

Figure 16

Single Flue - Horizontal Tall Vent Run

22618-4-1106

Page 19

Page 19
Image 19
GN National Electric PV-28SV55, PV-28SV50, GN, BP)-1, GP)-1, CP installation instructions Vent Examples for Single Flue