Goodman Mfg CPG SERIES Belt Drive Models Only, Three Phase Models Only, t = Span length, inches

Models: CPG SERIES

1 56
Download 56 pages 48.63 Kb
Page 15
Image 15
Three Phase Models Only

System Voltage - That nominal voltage value assigned to a circuit or system for the purpose of designating its voltage class.

Nameplate Voltage - That voltage assigned to a piece of equipment for the purpose of designating its voltage class and for the purpose of defining the minimum and maximum voltage at which the equipment will operate.

Utilization Voltage - The voltage of the line terminals of the equipment at which the equipment must give fully satisfac- tory performance. Once it is established that supply voltage will be maintained within the utilization range under all sys- tem conditions, check and calculate if an unbalanced condi- tion exists between phases. Calculate percent voltage un- balance as follows.

Three Phase Models Only

 

 

2) MAXIMUM VOLTAGE DEVIATIONS

3) PERCENT VOLTAGE

= 100 X

 

FROM AVERAGE VOLTAGE

 

UNBALANCE

 

 

1) AVERAGE VOLTAGE

 

 

 

HOW TO USE THE FORMULA:

EXAMPLE: With voltage of 220, 216, and 213

1)Average Voltage = 220+216+213=649 / 3 = 216

2)Maximum Voltage Deviations from Average Voltage = 220 - 216 = 4

3) Percent Voltage Unbalance = 100 x

4

=

400

= 1.8%

216

216

 

 

 

Percent voltage unbalance MUST NOT exceed 2%.

FIELD DUCT CONNECTIONS

Verify that all duct connections are tight and that there is no air bypass between supply and return.

CONTROL VOLTAGE CHECK

With disconnect switch in the open “OFF” position, discon- nect blue wire from low voltage transformer TRANS1. Close the disconnect switch to energize TRANS1 control trans- former. Check primary and secondary (24V) of control trans- former TRANS1.

THERMOSTAT PRELIMINARY CHECK

With disconnect switch open and blue wire disconnected from TRANS1 transformer, attach one lead of ohmmeter to termi- nal R on TB1 terminal block. Touch, in order, the other ohm- meter lead to terminals Y1, Y2 and G at TB1 terminal block. There must be continuity from terminal R to terminals Y and G. R to Y indicates cool. R to G indicates fan (auto). Replace blue wire on TRANS1 transformer.

FILTER SECTION CHECK

Remove filter section access panels and check that filters are properly installed. Note airflow arrows on filter frames.

BELT DRIVE MODELS ONLY

BEARING CHECK

Prior to energizing any fans, check and make sure that all setscrews are tight so that bearings are properly secured to shafts.

SET EVAPORATOR FAN RPM

Actual RPM’s must be set and verified with a tachometer or strobe light. Refer to Appendices A and B for basic unit fan RPM. Refer also to “Airflow” section of this manual. With disconnect switch open, disconnect thermostat wires from terminals Y and W. This will prevent heating and mechanical cooling from coming on. Place a jumper wire across termi- nals R and G at TB1 terminal block. Close disconnect switch; evaporator fan motor will operate so RPM can be checked.

For gas heat units, the airflow must be adjusted so that the air temperature rise falls within the ranges given stated on Data Plate (see Appendix A - Blower Performance).

TENSION AND ALIGNMENT ADJUSTMENT

Correct belt tension is very important to the life of your belt. Too loose a belt will shorten its life; too tight, premature mo- tor and bearing failure will occur. Check you belt drive for adequate “run-in” belt tension by measuring the force required to deflect the belt at the midpoint of the span length. Belt tension force can be measured using a belt tension gauge, available through most belt drive manufacturers.

Belt Tension Adjustment

t = Span length, inches

C = Center distance, inches

D = Larger sheave diameter, inches d = Smaller sheave diameter, inches

h = Deflection height, inches

TYPE

SMALL

DEFLECTION

 

DEFLECTION

SHEAVE

 

FORCE (lbs)

 

 

 

DIAMETER

 

(in)

 

 

 

 

 

BELT

DRIVE

(in)

USED

NEW

 

 

 

 

 

 

 

 

AX

Standard

3.0 to 4.0

4.2 ± 0.5

5.5 ± 0

.5

0.313

Recommended Pounds of Force Per Belt

New V-belts will drop rapidly during the first few hours of use. Check tension frequently during the first 24 hours of opera- tion. Tension should fall between the minimum and maximum force. To determine the deflection distance from a normal position, measure the distance from sheave to sheave using a straightedge or a cord. This is your reference line. On mul- tiple belt drives, an adjacent undeflected belt can be used as a reference.

15

Page 15
Image 15
Goodman Mfg CPG SERIES installation manual Belt Drive Models Only, Three Phase Models Only, t = Span length, inches