INPUT RATING

Pressure Switch Stuck Open

A pressure switch stuck open can be caused by a faulty pres- sure switch, faulty wiring, a disconnected or damaged hose, a blocked or restricted flue, or a faulty induced draft blower.

If the control senses an open pressure switch during the pre- purge cycle, the induced draft blower only will be energized. If the pressure switch opens after ignition has begun the gas valve is deenergized, the circulator blower heat off cycle be- gins, and the induced draft blower remains on. The diagnos- tic fault code is two flashes.

Pressure Switch Stuck Closed

A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring. If the control encounters a pressure switch stuck closed, the induced draft blower re- mains off. The diagnostic LED code for this fault is three (3) flashes.

Open Thermal Protection Device

If the primary limit switch opens, the gas valve is immediately deenergized, the induced draft and air circulating blowers are energized. The induced draft and air circulator blowers remain energized until the limit switch recloses. The diag- nostic fault code for an open limit is four (4) flashes.

A primary limit will open due to excessive supply air tempera- tures. This can be caused by a dirty filter, excessive duct

INPUT RATING

It is the responsibility of the contractor to adjust the gas input to the unit. The input rate can be calculated by using the formula:

INPUT Btu/Hr =

3600 x HV

T

 

WHERE:

HV = Heating value of fuel = Btu/ft3 of gas

T = Time in seconds per ft3 of gas flow as read from gas meter

Adjust input rate by varying the adjustment of the gas pres- sure regulator on the gas valve. All adjustments must be made with furnace operating at high fire and at normal operating temperature. Clockwise (P) rotation of the pressure regula- tor screw increases pressure and gas flow rate. Turn screw counterclockwise (Q) to decrease pressure and gas flow rate. After adjustment the furnace temperature rise must be within the range specified on the unit data plate. NOTE: Thermal efficiency of the furnace is a product efficiency rating deter- mined under continuous operating conditions independent of any installed system.

Outlet Pressure

Pressure Regulator

Adjustment

Tap

(Under Cap Screw)

static, insufficient air flow, or a faulty limit. Check filters, total external duct static, blower motor, blower motor speed tap (see wiring diagram), and limit. This limit will automatically reset once the temperature falls below a preset level.

Flame Detected with Gas Valve Closed

If flame is detected with the gas valve deenergized, the com- bustion and air circulator blowers are energized. The diag- nostic fault code is five (5) flashes for this condition. The control can be reset by removing the power supply to the unit

INLETINLET

Inlet Pressure

Tap

 OUTLET OUTLET

Gas Valve

On/Off

Selector

Switch

or it will automatically reset after one hour. Miswiring is the probable cause for this fault.

ABNORMAL OPERATION - COOLING

Short Cycle Compressor Delay

White-Rodgers 36G22 - Single Stage

Open to

Manometer

 

 

Atmosphere

Hose

 

 

 

 

 

 

 

High Fire Regulator

 

 

Outlet

Adjust

Regulator

 

Pressure Boss

 

Vent

The automatic ignition control has a built-in feature that pre- vents damage to the compressor in short cycling situations. In the event of intermittent power losses or intermittent ther- mostat operation, the ignition control will delay output to the compressor contactor for three minutes from the time power is restored. (Compressor is off a total of three minutes). The diagnostic LED will flash six (6) times to indicate the com- pressor contactor output is being delayed.

NOTE: Some electronic thermostats also have a built-in compressor short cycle timer that may be longer than the three minute delay given above. If you are using an electronic

Inlet

Pressure Boss

Manometer

Low Fire

Regulator Adjust

thermostat and the compressor has not started after three minutes, wait an additional five minutes to allow the thermostat to complete its short cycle delay time.

White-Rodgers 36G54 (2-Stage) Connected to Manometer

Pressure Adjustments

21