Goodman Mfg CPG SERIES High Static Down Shot, Appendix A Blower Performance Tables Belt Drive

Models: CPG SERIES

1 56
Download 56 pages 48.63 Kb
Page 31
Image 31

APPENDIX A BLOWER PERFORMANCE TABLES

BELT DRIVE

HIGH STATIC DOWN SHOT

CPG036 HIGH STATIC BELT DRIVE DOWN SHOT

ESP, In

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

1

 

2

 

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

1655

 

0.526

1389

 

0.395

1103

 

0.275

0.8

 

 

 

 

 

 

 

1640

 

0.571

1342

 

0.426

1035

 

0.289

775

 

0.19

1.0

 

 

 

 

1638

 

0.632

1326

 

0.471

1002

 

0.317

713

 

0.192

 

 

 

1.2

 

1638

 

0.692

1307

 

0.519

984

 

0.362

 

 

 

 

 

 

 

 

 

1.4

 

1307

 

0.579

1002

 

0.416

 

 

 

 

 

 

 

 

 

 

 

 

1.6

 

1002

 

0.476

717

 

0.319

 

 

 

 

 

 

 

 

 

 

 

 

1.8

 

717

 

0.379

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPG048 HIGH STATIC BELT DRIVE DOWN SHOT

ESP, In

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

 

0

1

 

2

 

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

1989

 

0.769

1712

 

0.594

1433

 

0.441

0.8

 

 

 

 

 

 

 

1929

 

0.788

1662

 

0.631

1384

 

0.469

1106

 

0.329

1.0

 

 

 

 

1952

 

0.876

1622

 

0.665

1335

 

0.494

1056

 

0.345

 

 

 

1.2

 

1897

 

0.93

1611

 

0.726

1315

 

0.543

1008

 

0.357

 

 

 

 

 

 

1.4

 

1616

 

0.80

1298

 

0.588

1007

 

0.419

 

 

 

 

 

 

 

 

 

1.6

 

1316

 

0.659

1007

 

0.46

 

 

 

 

 

 

 

 

 

 

 

 

1.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPG060 HIGH STATIC BELT DRIVE DOWN SHOT

ESP, In

 

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

 

1

 

2

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

BHP

CFM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

2262

 

1.161

2051

 

0.948

1851

 

0.763

1657

 

0.60

0.8

 

 

 

 

2277

 

1.271

2070

 

1.048

1852

 

0.837

1646

 

0.656

 

 

 

1.0

 

2304

 

1.387

2089

 

1.153

1872

 

0.931

1647

 

0.722

 

 

 

 

 

 

1.2

 

2104

 

1.255

1893

 

1.029

1668

 

0.811

 

 

 

 

 

 

 

 

 

1.4

 

1912

 

1.129

1690

 

0.90

 

 

 

 

 

 

 

 

 

 

 

 

1.6

 

1720

 

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPG072 HIGH STATIC BELT DRIVE DOWN SHOT

ESP, In

 

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

 

1

 

2

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

BHP

CFM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

2793

 

1.645

2575

 

1.367

2407

 

1.155

2250

 

0.963

0.8

 

 

 

 

2775

 

1.762

2638

 

1.526

2407

 

1.253

2226

 

1.045

2011

 

0.835

1.0

 

2821

 

1.894

2660

 

1.668

2407

 

1.358

2194

 

1.116

2012

 

0.923

 

 

 

1.2

 

2696

 

1.787

2497

 

1.54

2228

 

1.235

1977

 

0.985

 

 

 

 

 

 

1.4

 

2455

 

1.591

2236

 

1.346

2013

 

1.10

 

 

 

 

 

 

 

 

 

1.6

 

2262

 

1.44

2032

 

1.20

 

 

 

 

 

 

 

 

 

 

 

 

1.8

 

2069

 

1.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

31

Page 31
Image 31
Goodman Mfg CPG SERIES installation manual High Static Down Shot, Appendix A Blower Performance Tables Belt Drive